Nobody draws a utility feeder by hand. File → Import .dss… reads an OpenDSS model; File → Import from reads GIS layers and CSV tables, and, with the converter plugin, CYME and Synergi models.

OpenDSS files

  1. Choose File → Import .dss….
  2. Select your main .dss file plus any files it redirects to (linecode libraries, load definitions, bus coordinate files — select them all together in the file dialog). Selecting a whole folder is fine: the importer follows the redirects from the file that defines the circuit, leaves out files that are not part of it, and says so if the folder holds two masters (a balanced and an unbalanced case, say).
  3. The circuit appears laid out as a top-down tree: source at the top, loads in a row beneath their buses, buses sized to fit. It is the same layout Arrange → Clean up layout applies (in the direction set under Arrange → Layout direction), so you can always get back to it. From there it's a normal project — edit, solve, save as .oneline.json, or re-export. If the file has bus coordinates, Map (top right of the drawing) shows it on the ground (see The map).

How it works

Rather than re-implementing a DSS parser, the importer hands your files to OpenDSS's own parser (via OpenDSSDirect.py), compiles the circuit, and reads the resulting model back out element by element. That means anything OpenDSS itself accepts — abbreviations, mixed case, line continuations — is understood, and the parameters you see are the values OpenDSS actually used.

Supported elements

Import maps Vsource, Line and LineCode (a line keeps its code, matrix and all; a line built from a LineGeometry gets a code named after the geometry, and one that wrote its own matrix, or named a code with a different phase count, gets a code of its own name), Transformer (two or three windings, with their taps, no-load loss, magnetising current and per-winding resistance; an equal-ratio transformer with a RegControl becomes a regulator, while a controlled transformer that changes voltage — a substation LTC — stays a transformer and keeps its control), switches (a Line with switch=yes; one operated by a Fuse, Recloser or overcurrent Relay becomes that device), series Reactors (drawn as a line, written back as a reactor), Load (with its CVR or ZIP coefficients), Capacitor, Generator, PVSystem, Storage, LoadShape and TCC_Curve onto diagram elements.

Three things about real feeders are carried across too:

  • Elements the file disabled (enabled=no — open ties, spare connectors) are drawn dashed and out of service. Tick In service in the properties panel to put one back.
  • The file's voltage bases (set voltagebases=[...]) are kept, under File → Project properties, so every bus reads in per unit against the base the file chose. Without them a 120/240 V service would read 1.73 pu.
  • Bus coordinates (BusCoords, LatLongCoords) are kept exactly as the file gave them, and written back on export as SetBusXY.

The validation page measures all of this: the IEEE 13, 34, 37 and 123-bus feeders and EPRI's ckt5, ckt7, ckt24 and the IEEE 8500-node feeder import and solve to within 0.0002 pu of OpenDSS's own solution of the original files.

Large feeders

A circuit of more than about 1,500 elements is drawn more sparingly so that it stays quick: zoomed out, it is an overview — every line and bus on one canvas, coloured by the overlay that is on — and the symbols appear as you zoom in, only those in view. Clean up lays such a circuit out as a tidy tree, the trunk running straight down and laterals branching off either side. A 10,000-element feeder imports, lays out and draws in about two seconds and solves in about one.

Everything else: passthrough elements and comments

Anything else in the file — monitors, energy meters, capacitor and inverter controls, XY curves, a shunt reactor, a four-winding transformer — is kept as the file wrote it, in the order it was defined, and listed in the Passthrough tab. It is written back on export, and it runs in every solve after the elements on the drawing, so a CapControl still switches its capacitor and a Reactor still grounds its bus. The tab lets you read, edit or delete each one, or type in one of your own.

A few things keep a passthrough element out of the solve (it is still exported, and the Problems list says why):

  • it refers to something that is no longer in the circuit — a monitor on a line you deleted. Renaming an element in the editor rewrites the references to it, so a rename never causes this. On export the element is written commented out, so the file still compiles;
  • it reads a file (mult=(file=...), csvfile=), which the server does not have;
  • it is of a class outside a short list of measurement, control, curve and simple circuit objects, or it is anything other than New and Edit lines naming itself — a passthrough element is data, never a script;
  • the engine rejects it when the solve runs.

Comments come through too: the comment lines directly above an element, and a comment at the end of its line, are written back above it on export, and the comments at the top of the main file stay at the top.

GIS layers and CSV tables

File → Import from → GIS layers or CSV tables… reads Esri shapefiles (select the .shp, .dbf and .prj together, or a .zip of them), GeoJSON and CSV. For each layer:

  1. Say what it is: a line (conductor) layer, switches, fuses, reclosers, transformers, loads, capacitors, generators, PV, storage, the source (substation), a table of line codes or a table of bus coordinates. The class is guessed from the layer's name.
  2. Say which column holds what. Columns are matched to properties by name, including the names GIS exports commonly use (FACILITYID, PHASE, KVA_RATING, NORMALSTATUS…). Any property can instead be given one value for the whole layer — every load at 0.24 kV, say — and anything left blank takes the default shown. The mapping is remembered, so the next export of the same layer imports in one click.

Where the tables have bus columns (from/to bus, or a load's bus), they decide the connections. Where they do not, as in most GIS exports, the geometry does:

  • line ends closer than the snap tolerance are one bus;
  • a device drawn as a point attaches to the nearest bus within the attach radius, a customer preferring a transformer's secondary; a load layer can also name its transformer in a column;
  • a switch, fuse, recloser or transformer drawn as a point is inserted where it stands, with everything downstream of it — away from the source — moved to its far side.

Single-phase transformers and loads recorded at the system's line-to-line voltage are rated line-to-neutral; lines with no impedance and no line code get typical overhead values. All of it is reported, along with anything left out or not connected to the source (usually a snap tolerance too tight for line ends that nearly meet). The layers' coordinate system comes with them — a shapefile's .prj, or WGS 84 for GeoJSON — so the result appears on the map.

What the import builds is an ordinary OpenDSS model, read by the same importer as a .dss file; File → Export → OpenDSS (.dss) writes it out for use anywhere else.

CYME and Synergi

File → Import from → CYME… / Synergi… convert those tools' models with opendss-designer-convert, an optional plugin (a revived fork of NREL's DiTTo, BSD-licensed, kept in its own repository because of its GIS-sized dependencies). Install it beside the app — Python 3.11 or later:

pip install opendss-designer-convert

then restart OpenDSS Designer. Without it the menu says how to get it. On the hosted instance the plugin is installed and the import is part of the Pro plan: the menu lists CYME and Synergi for everyone, and says so when clicked on another plan. For CYME, select the network, equipment and load exports together; for Synergi, the model's .mdb and its warehouse .mdb. The converted model is imported like a .dss file, with the converter's notes (what it could not carry across) in the import message.

Verified so far against the converter's own samples: CYME 5.04 and 8.00 exports of the IEEE 13 and 123-bus feeders, and one Synergi Electric 6.4 model. WindMil is not yet supported.

Note

Round-tripping is a design goal: export the imported circuit and you get a .dss file that solves to the same result. If you find a model that doesn't survive the round trip, please open an issue — ideally with the files attached.