Interoperability and power quality

CIM

File → Import from → CIM (IEC 61968-13 RDF/XML)… reads a CIM100 / CDPSM document: buses from ConnectivityNode and Terminal, ACLineSegment with its own impedance or a PerLengthSequenceImpedance / PerLengthPhaseImpedance (which becomes a line code), EnergyConsumer and its phases, EnergySource, PowerTransformer in the end form or the tank form with a RatioTapChanger as a regulator control, breakers, disconnectors, load-break switches, fuses, reclosers and sectionalisers, LinearShuntCompensator, PowerElectronicsConnection with photovoltaic or battery units, SynchronousMachine, and Location / PositionPoint coordinates with the CoordinateSystem. It is turned into OpenDSS text and goes through the ordinary importer, so the notes it leaves are the importer's. File → Export → CIM writes the same classes from the drawing.

MultiSpeak

File → Import from → MultiSpeak network model… reads the co-operative utilities' exchange format (versions 3 and 4 as WindMil and most co-op GIS products write it): overhead and underground line sections, transformer banks, switches, fuses, reclosers, sectionalizers, capacitor banks, substations and meters, joined by their section and parent-section ids, with GPS coordinates. Field names are matched case-insensitively and by common synonyms. Conductor types are kept as comments and the line impedances are typical values until a line code is assigned. The reader was written from the specification and checked against a synthetic sample only; a real export is wanted to confirm it.

Results to GIS

File → Export → Results to GIS writes every bus and line that has coordinates with what the last studies said about it — voltage, loading, power, losses, hosting capacity and its binding criterion, reliability section, phases — as GeoJSON (points and line strings in the project's coordinate system), CSV or KML (which expects WGS84 and says so when the project is not). It is how a hosting-capacity map or a voltage map gets into a utility's GIS or onto a public page.

Power quality

Studies → Power quality runs the harmonic study: the circuit is solved at each harmonic order in turn (mode=harmonics), every load, generator and PV system injecting by its spectrum (the engine's defaults unless a project spectrum is named through a passthrough Spectrum), and the voltage THD at every bus with the worst single harmonic is held to IEEE 519 (5 % THD and 3 % individual below 69 kV). And rapid voltage change: the voltage step at every bus when a motor starts (a locked-rotor load at a low power factor, switched on) or a DER unit trips, against the IEEE 1453 / 1547-2018 limit (3 % by default).

Python API and command line

Every study is a function of a Circuit and an options dict in opendss_designer.studies (run_study(name, circuit, options); STUDIES lists them), the same code the REST routes call, so a script or the desktop app runs them in-process. opendss-designer run runs them from the shell on a saved project; see the API page. The REST routes are documented live at /docs on a running server.

What has been checked

tests/test_m17.py holds: a hand-written CIM sample with every supported class imports and solves with the expected elements, impedances and coordinates; the schema fixture exported to CIM and imported back keeps its loads, lines and transformers and draws the same power within 10 %; a MultiSpeak sample imports with its devices, open switch, service transformer and coordinates and solves; the harmonic study reports a THD and a spectrum at every bus; a DER trip and a motor start give voltage steps of the right sign; and the run command writes the studies' JSON.